EM500 Open-Loop Vector Control Inverter User Manual When F25.38 is set to 2, the water level is detected by analog quantity and the analog channel is selected by F25.39. Water level processing logic: 1. When the upper limit water level, lower limit water level and water level switch are set.

When the water level changes from high to low, the water level is higher than the lower limit of water level, the system operates according to the normal set pressure; when the water level is lower than the lower water level and higher than the water level, the system operates according to abnormal standby pressure; Water level, the system shut down When the water level changes from low to high, the system will not run when the water level is lower than the lower limit. It will run at normally set pressure. 2. Only when the upper limit water level and the lower limit water level switch are set. When the water level is lower than the lower water level, the system is in standby.

When the water level is higher than the upper limit water level, the system automatically resume operation. Analog input value into switching states as follows: 317 No. Function Range Unit Default Type F25.39 The water level signal analog input channel selection 0: AI1 1: AI2 2: AI3 3: AI4 4: HDI 5: Communications input 2 〇 F25.40 Upper Limit water level analog level 0.0~100.0 % 60.0 ● F25.41 Lower Limit water level analog level 0.0~100 % 40.0 ● F25.42 Shortage of water water level analog level 0.0~100.0 % 20.0 ●