EM500 Open-Loop Vector Control Inverter User Manual F27.20 Ones Place=0: The wire cut is detected by the inverter automatically. This method requires F09.35 and F09.36 to be set correctly. F27.20 Ones Place=1: The wire cut is detected by an external proximity switch. F27.20 Tens Place=0: When the stop command is received, if the output frequency is less than the setting value of F27.22, no wire cut detection is performed. F27.20 Tens Place=1: Wire cut detection is not performed. F27.20 Hundreds place=0: After wire cut, press F 27.24 to set the frequency to continue running, only 68 function terminals and fault output terminal action. F27.20 Hundreds place=1:
After the wire cut, the function terminal and the fault output terminal of No. 68 are actuated, and stop after F27.23 time and F27.24 frequency and enter into the fault state. F27.20 Hundreds place=2: After the wire cut, the inverter enters the fault state F27.20 Thousands place=0: Mode 0: The brake does not operate when the output frequency is traversed from the top down through the brake output frequency (F27.25). F27.20 Thousands place=1: Mode 1: The brake operates when the output frequency is traversed from the top down through the brake output frequency (F27.25). F27.20 Myriabit=0: Reverse no speed limit. F27.20 Myriabit=1:
335 0:Only Error terminal movement 1:Parking time delay and Error 2:Material supply disruptions Error Thousands place:Brake mode 0:Mode 0 1:Mode 1 myriabit: unwinding reverse mode 0:unrestricted speed 1:According to the F27.24 reverse speed limit