EM500 Open-Loop Vector Control Inverter User Manual Reverse press F27.24 speed limit. After the inverter receives the running command, it will start disconnection detection after the set time. If the F27.20 tens place is set to 0, the inverter will not perform wire cut detection after it decelerates to this frequency (The output frequency of the inverter must be lower than this frequency after the soft start time exceeds this frequency and then the function will be effective) The time set in F7.23 starts to count since wire cut is judged. At this time, the running frequency follows the setting of F27.24. For unwinding, it is reverse, for winding, it is forward.
F27.25 and F27.26 are valid only when an output terminal is defined as "brake control" (function code 67),when the inverter output frequency falls from the top to the set value of F27.25, the brake control terminal is valid and maintained (brake mode 1 active). It becomes invalid after the setting time of F27.26. When the brake control terminal 336 No. Function Range Unit Default Type F27.21 Material supply disruptions Detection delay 0.0~10.0 s 6.0 ● No. Function Range Unit Default Type F27.22 The lower limit of material supply interruption detection when parking 0.00~60.00 Hz 5.00 ● No.
Function Range Unit Default Type F27.23 Continue to running time after the material supply disruptions 0.0~60.0 s 10.0 ● F27.24 Continue-to-run Frequency after the material supply disruptions 0.00~Fmax Hz 5.00 ● No. Function Range Unit Default Type F27.25 Brake signal output frequency 0.00~Fup Hz 2.50 ● F27.26 Brake signal duration 0.0~100.0 s 5.0 ●