sinee — 7.24 F28 Air Compressor Application

EM500 Open-Loop Vector Control Inverter User Manual starts when remote control is engaged, and shut down when disengaged, at this time, local control is invalid F28.02=0: Automatic 1, When the feedback pressure is less than the lower limit pressure, automatically loaded, when greater than the upper limit pressure, automatically reducing load. 2, When the feedback pressure is less than the lower limit pressure, loaded automatically, can not manually unload. 3, When the feedback pressure is greater than the upper limit pressure, press loading button, can automatically load the set time in F28.54, after loading, automatically unloaded.

4, When the feedback pressure is greater than the pre-warning pressure, the system will be automatically unloaded 5, The pressure between the upper and lower limits can be manually loaded and unloaded 6, After initial start, automatically loaded F28.02=1: Manual: Initial start-up is in unloaded state After loading, if pressure is greater than the upper limit, the system will be automatically unloaded. If lower than upper limit pressure, can manually load or unload. F 28.03 is the effective minimum frequency for output function code 49 340 No. Function Range Unit Default Type 0: Automatic F28.02 Loading way 0 〇 1: Manual No.

Function Range Unit Default Type Loading Lower F28.03 0.00~Fup Hz 25.00 ● limit Frequency No. Function Range Unit Default Type Manual loading 0: Clear and unload F28.04 0 ● control command 1:To 1 Load