sinee — 7.24 F28 Air Compressor Application

EM500 Open-Loop Vector Control Inverter User Manual F 28.04 will change as per the present state, clear and unload, for To 1 Load, RAM is effective upon the change. 1. Valve terminal function corresponds to output terminal function code 49 When the inverter remains in unloading state, if the running time reaches at this time, the system will stop automatically. The inverter running frequency in unloading state When the compressor stops, stops by long wait, and faulty to stop, it needs to wait for this time before receiving start command. If running in the loaded state, the valve will close immediately after receiving the stop command. The system will delay the time of F28.08.

When it receives the shutdown command, it will stop directly. F28.10 port corresponds to the gauge’s maximum range F28.09. 341 No. Function Range Unit Default Type F28.05 Dormancy Delay 10~7200 s 1200 ● No. Function Range Unit Default Type Unloading F28.06 operation 0.00~Fup Hz 20.0 ● frequency No. Function Range Unit Default Type Shutdown and F28.07 1~300 s 60 ● restart delay time No. Function Range Unit Default Type Shutdown delay F28.08 0~60000 s 5 ● time No. Function Range Unit Default Type Maximum F28.09 0.5~25.00 MPa 1.60 〇 pressure range 0: AI1 1: AI2 Pressure feedback F28.10 2: AI3 0 〇 selection 3: AI4 4: HDI Pressure Digital F28.11 0.00~Upper Limit Pressure value MPa 0.80 ● given