EM500 Open-Loop Vector Control Inverter User Manual Early-warning pressure: When the feedback pressure is greater than the warning pressure, the inverter must perform the unloading Warning pressure: When the feedback pressure is greater than the set value, the system will report E45 fault Adjust PID control parameters according to the actual application. F28.18 / F28.19 control upper limit and lower limit of pressure PID output respectively. These codes are used for system loading or unloading control and part of parameters limiting. In the meanwhile, these codes are judge condition for loading or unloading, e.g.
unloading when greater than the upper limit pressure value, loading when smaller than 342 No. Function Range Unit Default Type Early-warning Pressure Digital setting~ Warning F28.12 MPa 0.98 ● pressure pressure Early-warning pressure~ F28.13 Warning pressure MPa 1.00 ● Maximum pressure range No. Function Range Unit Default Type Pressure F28.14 proportional gain 0.00~100.00 5.00 ● GP Pressure integral F28.15 0.000~60.000, 0.000:
No Integral s 10.000 ● time GTi Pressure F28.16 differential time 0.000~60.000 ms 0.000 ● GTd Pressure integral F28.17 0.00~100.00 % 100.00 ● action range Pressure F28.18 Regulation Upper 0.00~100.00 % 100.00 ● Limit Pressure regulation F28.19 0.00~100.00 % 25.00 ● Lower Limit No. Function Range Unit Default Type lower Limit F28.20 0.00~ Upper Limit pressure value MPa 0.75 ● pressure value Upper Limit lower Limit pressure value~ F28.21 MPa 0.85 ● pressure value Maximum pressure range