sinee — 9.2 Warning Analysis

EM500 Open-Loop Vector Control Inverter User Manual 364 C002 The pump feedback is disconnected Available only in water supply applications 1. 1. This warning is displayed when the feedback disconnection method is selected to maintain the current status and the disconnection condition is satisfied. 1. Check whether the sensor is abnormal 2. Check if the analog input terminals are abnormal C003 Pipe network overpressure Available only in water supply applications 1. This warning is displayed when the pressure of the water supply pipe network is too high and the overpressure treatment mode is selected as no alarm. 1. Check if the sensor is abnormal 2.

Check if the analog input terminals are damaged C004 Water supply pool water shortage Available only in water supply applications 1. If the water supply level control function is enabled, if the water level input terminal is included, this warning is displayed if the water level input terminal is disconnected after the inverter is running. 1. Check if the input terminals corresponding to the water level are damaged C005 Motor overload during rotation Available only in water supply applications 1.

The frequency converter displays this warning when a water supply application is in the switching mode of the Primary pump plus standby pump and the motor is overloaded when one of the pumps is driven. 1. Check if the load is too heavy C006 Output phase loss during rotation Available only in water supply applications 1. The frequency converter displays this warning when a water supply application is in the switching mode of the Primary pump plus standby pump and an output phase loss occurs while driving one of the pumps. 1. Check whether the output wiring is loose