EM500 Open-Loop Vector Control Inverter User Manual P, Ti and Td of PID controller do not match in setting properly. Reset PID parameters. 9.3.8Inverter Stops Output While Motor Still Rotates Insufficient DC Brake at Stop DC brake torque at stop is too small. Please increase the set value of DC brake current at stop (F04.21). DC Brake Time at Stop is too short. Please increase DC brake time at stop 9.3.9Output Frequency Not As Per the Set Frequency (F04.22). Generally speaking, increase DC brake current at stop first. The set frequency exceeds the upper limit frequency.
If the set frequency exceeds the set value of the upper limit frequency, then output frequency should be the upper limit frequency. Reset the set frequency within the upper limit frequency; or check whether F00.16, F00.17 and F00.18 are appropriate. 368