sinee — 11.3 Options of Cable

EM500 Open-Loop Vector Control Inverter User Manual ★ The cable listed above refers to outgoing line of individual resistor. When resistor is connected in parallel, the bus in connection should be amplified accordingly. Single-phase inverter selects voltage withstanding type cable of AC300 V, 3-phase inverter uses cable of over AC450V and temperature resistance 105 ℃ . 11.2 Braking Unit our BR100 braking units (power range: 18.5 – 315 kW). Models of braking units are If EM500 inverter (over 18.5 kW) has no built-in braking unit, then user shall select listed below: ★ When BR100-106 adopts minimum resistance, if braking frequency of braking unit D=33%, it can continue to work.

If D>33%, it needs to work intermittently, otherwise an overheat protection fault will occur. 11.3 Options of Cable Because all the braking units and braking resistors wok at high voltage (>400VDC) discontinuously, please select the appropriate cable. See Table 11-1 for specification of the cable of the main circuit. During wiring, only those cable with the insulation grade and the section meeting standards should be used.

373 EM500-2R2G/3R0P-1B/2B/3B 2.2 ≧180 ≧400 1.5 EM500-4R0G/5R5P-3B 4 ≧90 ≧800 2.5 EM500-5R5G/7R5P-3B 5.5 ≧60 ≧1000 4 EM500-7R5G/9R0P-3B 7.5 ≧60 ≧1000 4 EM500-011G/015P-3B 11 ≧30 ≧2000 6 EM500-015G/018P-3B 15 ≧30 ≧2000 6 EM500-018G/022P-3B 18.5 ≧30 ≧2000 6 EM500-022G/030P-3/3B 22 ≧15 ≧4000 6 EM500-030G/037P-3/3B 30 ≧15 ≧4000 6 EM500-037G/045P-3/3B 37 ≧10 ≧6000 6 EM500-045G/055P-3/3B 45 ≧10 ≧6000 6 EM500-055G/075P-3/3B 55 ≧7.5 ≧8000 6 EM500-075G/090P-3/3B 75 ≧6 ≧8000 6 Minimum resistance Average braking Peak current Inverter power Model No. (Ω) current I (A) av I (A) max (kW) BR100-045 10 45 75 18.5 - 45 BR100-160 6 75 150 55 - 160 BR100-315 3 120 300 185 - 315