sinee — 12.3.4Allocation of Register Address

EM500 Open-Loop Vector Control Inverter User Manual 393 By function code of 0x06 or 0x10 to set parameter “original address + 8000H” will be “effect immediately and not to save after power off”.

For example F00.14, its address is 800EH (000EH + 8000H) Function Code (not to save after power off) 8000H~EF63H 7000H Control Word 0000H Disabled Command 0001H Forward Running 0002H Reverse Running 0003H Forward JOG 0004H Reverse JOG 0005H Ramp-To-Stop 0006H Rapid Stop 0007H Coast-to-Stop 0008H Fault Reset 0009H +/-Input Switch 000BH JOG Stop Other - 00FFH Not Used 7001H Main Channel Frequency A Communication Setting -100.00% - 100.00% (100%= maximum frequency) Control Comma nd 7002H Auxiliary Channel Frequency B Communication Setting -100.00% - 100.00% (100%= maximum frequency) (Write Only) 7000H - 7003H Torque Communication Setting -200.00% - 200.00% (100%=Numeric Setting) 71FFH 7004H Process PID Communication Setting -100.00% - 100.00% 7005H Process PID Feedback Communication Setting -100.00% - 100.00% 7006H VF separation mode voltage setting 0.00% - 100.00%(Numeric Setting Reference) 7007H - 7009H Not Used 700AH Upper Limit 0.00% - 200.00%(Numeric Setting