sinee — 12.3.4Allocation of Register Address

EM500 Open-Loop Vector Control Inverter User Manual The following is an example of requesting to write 00 01 and 00 03 in the two registers starting from F03.00, i.e., setting the functions of output terminals Y1 and Y2 ★ Those function codes of inverter that are frequently changed can not complete this function with the function code 0x10 to avoid damaging inverter. Refer to 12.3.3.5 for details.

12.3.4Allocation of Register Address Table 12-2 MODBUS Protocol Register Address Definitions 392 Request Response Field Name (0x) Field Name (0x) Field Name (0x) (normal) (abnormal) Function 10 Function 10 Function 90 Initial Address Hi 03 Initial Address 03 03 Hi Exceptional Initial Address Lo 00 Initial Address 00 Code Lo Number of Registers 00 Number of 00 Hi Registers Hi Number of Registers 02 Number of 02 Lo Registers Lo Number of Bytes 04 Register Value Hi 00 (F03.00) Register Value Lo 01 (F03.00) Register Value Hi 00 (F03.01) Register Value Lo 03 (F03.01) Address Space Description For function codes FXX.YY, their high addresses are in hexadecimal format of XX and their low addresses are in hexadecimal format of YY.

For example F00.14, its address is 000EH (00D=00H, 14D=0EH). Function Code 0000H - 6F63H