EM500 Open-Loop Vector Control Inverter User Manual take effect immediately, but will not be saved in EEPROM. After rewriting, inverter runs The data above means to change the set frequency (F00.07) to 50.00Hz, which will at the frequency 50.00 Hz, but runs at the frequency set prior to change after inverter is power on 12.3.3.60x10 Write multiple registers or commands remote device. This function code is used to write continuous register blocks (1 to 16 registers) in a The value requested for writing is described in the request data field. Each register divides the data into two bytes number of registers written.
The normal response is to return the function code, the initial address and the Request PDU N*=Number of Registers Response PDU Incorrect PDU 391 Request Response Field Name (0x) Field Name (normal) (0x) Function 41 Function 41 Register Address Hi 00 Register Address Hi 00 Register Address Lo 07 Register Address Lo 07 Register Value Hi 13 Register Value Hi 13 Register Value Lo 88 Register Value Lo 88 Function Code 1 byte 0x10 Initial Address 2 bytes 0x0000 - 0xFFFF Number of Registers 2 bytes 1 - 16 Number of Bytes 1 byte 2×N* Register Value N*×2 bytes Function Code 1 byte 0x10 Initial Address 2 bytes 0x0000 - 0xFFFF Number of Registers 2 bytes 1 - 16 Error Code 1 byte 0x90 Exceptional Code 1 byte See Table12-4