EM500 Open-Loop Vector Control Inverter User Manual Response PDU Incorrect PDU The following is an example of requesting to change motor 1 drive control mode (F0 0.01) to 1: FVC: ★ Those function codes of inverter that are frequently changed can not complete this function with the function code 0x06 to avoid damaging inverter. 0x41 RAM & EEPROM, a user-defined function code, corresponds to the standard common function code 0x06; the definition of this function code is the same as corresponding standard function codes (in request, response and error PDU).
The only difference is that when this function code is enabled, only corresponding value of RAM is modified, without being saved to EEPROM (holding register). For those function codes that are often changed, like F00.07, it’s recommended to use the function code 0x41 (user may also operate 7001H directly by modifying main frequency source A, refer to 12.3.3.2 and 12.3.4 for details) to avoid damaging inverter. See the following descriptions for details.
390 Function Code 1 byte 0x06 Register Address 2 bytes 0x0000 - 0xFFFF Register Value 2 bytes 0x0000 - 0xFFFF Error Code 1 byte 0x86 Exceptional Code 1 byte See Table 12-4 Request Response Field Name (0x) Field Name (0x) Field Name (0x) (normal) (abnormal) Function 06 Function 06 Function 86 Register Address 00 Register 00 03 Hi Address Hi Exceptional Register Address 01 Register 01 Code Lo Address Lo Register Value Hi 00 Register Value 00 Hi Register Value Lo 01 Register Value 01 Lo