EM500 Open-Loop Vector Control Inverter User Manual 12.3.7Abnormal Information Response Master wants to receive a normal response after it sends a request to slave. Inquiry of master may results in the following four response situations: If slave has received a request without communication error and can handle the inquiry normally, slave will return a normal response; If slave has not received the request due to communication error, slave cannot return information. Slave will be seen as overtime ; If slave has received the request but detected a communication error (for example parity, address, frame error), it will not return a response.
Slave will be sited as overtime ; If slave has received the request without communication error but can not handle it (example: request to read a register which does not exist), it will return an abnormal response to report the actual situation of the error to master An abnormal response message has two fields that are different from the normal response: Function code field: in normal response, slave copies the original request function code from the appropriate function code field. MSB of all the function code is zero. In abnormal response, MSB of slave function code is 1. Abnormal response function code = normal function code +0x80 Data Field:
A slave can return data in the data field in normal response and return abnormal code in abnormal response. See Table 12-4 for definitions of exceptional codes. Table 12-4 Definitions of Exceptional Codes 403 Exceptional Name Definitions Code 01H Illegal function The function code received by slave exceeds the configured scope (refer to 12.3.3 Function Code) 02H Illegal data address The data address received by slave (inverter) is not a permitted address; especially, the combination of the start address and transmission length of the register is invalid