EM500 Open-Loop Vector Control Inverter User Manual 12.4 Protocol Description 12.4.1 Definitions of Time Interval of Interframe and Intraframe Time Interval A complete MODBUS message includes not only the required data unit, but also start and end marks. Therefore, as indicated in Figure 12-1 and Figure 12-3, an idle level with the transmission time equal to or greater than 3.5 characters is defined as the start mark, and the transmission will be deemed as abnormal if there is an idle level with transmission time greater than 1.5 characters during the message transmission. Specific start-end and abnormal interval time have something to do with bit rate (refer to Table 12-5).
If the bit rate is 9,600 bps, with sampling period of 1ms, then the start-end interval is an idle level greater than or equal to 4ms (3.5Ч10/9600=3.64≈4), the interval of exceptional data is the idle level with interval time among bits of one data frame greater than or equal to 2ms (1.5Ч10/9600 = 1.56≈2) but smaller than 4ms (idle level between normal data bits less than or equal to 1 ms) Table 12-5 Checklist of Time Interval and Bit Rate (when t modify =1 ms) 404 (refer to 12.3.4 Allocation of Register Address).
03H Illegal data frame As detected by slave (inverter), the inquiry data frame length or CRC parity is incorrect 04H Slave fault Unrecoverable mistake happened when slave (inverter) tries to execute require operation. The cause may include logic error or failure to write EEPROM. 05H Data exceeding the range Data received by slave (inverter) exceeds the scope of corresponding register: minimum - maximum. 06H Parameter: read only The present register is read only and can not be written 07H Parameter: not modified during running Inverter is in running status. The present register can not be written. If necessary, please stop inverter at first. 08H Parameter:
password protection The present register is password protected. Start-end Abnormal Bit rate interval T interval interval T abnormal Remarks (bps) (t ) modify (t ) modify 4800 8 4 Normal frame permits the idle point level ≤3ms; when an idle level≥8ms, it means the end of a data frame.