sinee — 12.4.3Modbus Response Delay

EM500 Open-Loop Vector Control Inverter User Manual Frame 1 Frame 2 Frame 3 t 0 Abnormal Frame Abnormal Frame At least 3.5 .5 characters At least 3.5 At least 3.5 characters 3.5 characters characters characters Figure 12-3 Correct and Incorrect Data Frames 12.4.2Data Frame Processing After receiving a data frame, the system should process it first to judge whether it is a legal frame sent to inverter. Then, check whether the data is correct and perform corresponding processing. If the received frame is illegal, it will not turn data; if the received frame is legal but incorrect, it will turn corresponding abnormality information frame. Legal frame:

meet address (inverter or broadcast) and length (not less than 3) conditions Correct frame: a correct frame is a legal frame, of which corresponding memory address is corrected, memory content is as defined and can be processed for the time being. 12.4.3Modbus Response Delay [7] (data on RS-485 network, different from the command sent by the keyboard), to data learning, and then to starting the data return, as the response delay (set through F10.04).

Since a standard protocol has defined the start and end marks, there must be response delay, at least 3.5 character time interval +1ms (485 protocol chip stable time, t w2 ), and the specific minimum time interval has something to do with the bit rate. If bit rate is 9600 bps, the minimum response delay shall be 5 ms (3.5Ч10/9600+1=4.64≈5). Define the time interval from the receipt of a valid data frame If the communication data involves the EEPROM operation, the actual time interval will be extended 405 9600 4 2 Normal frame permits the idle point level ≤1ms; when an idle level≥4ms, it means the end of a data frame.

19200 2 1 Normal frame permits the idle point level<1ms; when an idle level≥2ms, it means the end of a data frame. Higher 1 1 An idle level of 1ms means the end of a data frame.