EM500 Open-Loop Vector Control Inverter User Manual 82 F02.00 X1 Numeric Input Function 0: No Function 1: Run Terminal “RUN” 2: Direction R/F 3: 3-Wire Sequence Stop Control 4: Forward JOG (FJOG) 5: Reverse JOG (RJOG) 6: Terminal UP 7: Terminal DOWN 8: Clear UP/Down Offset 9: Coast to Stop 10: Fault Reset 11: Preset Speed Terminal 1 12: Preset Speed Terminal 2 13: Preset Speed Terminal 3 14: Preset Speed Terminal 4 15: Preset PID Terminal 1 16: Preset PID Terminal 2 17: Preset Torque Terminal 1 18: Preset Torque Terminal 2 19: Acceleration/Deceleration Time Terminal 1 20: Acceleration/Deceleration Time Terminal 2 21: Acceleration/Deceleration Time Terminal Disabled 22: Operation Pause 23:
External Fault Input 24: Switch Run Command to Keypad 25: Switch Run Command to Communication 26: Frequency Source Switching 27: Clear Timed Running time 28: Switch between Speed Control and Torque Control 29: Torque Control Disabled 30: Switch between Motor 1 and Motor 2 31: Simple PLC Status Reset (Start to Run with Preset Speed 1, Clear Running time) 32:
Simple PLC Time Pause (Keep 1 〇 F02.01 X2 Numeric Input Function 2 〇 F02.02 X3 Numeric Input Function 11 〇 F02.03 X4 Numeric Input Function 12 〇 F02.04 X5 Numeric Input Function 13 〇 F02.05 X6 Numeric Input Function 14 〇 F02.06 X7 Numeric Input Function 10 〇 F02.07 AI1 Numeric Input Function 0 〇 F02.08 AI2 Numeric Input Function 0 〇 F02.09 AI3 Numeric Input Function 0 〇 F02.10 AI4 Numeric Input Function (Expansion Card) 0 〇 F02.11 X8 Numeric Input Function (Expansion Card) 0 〇 F02.12 X9 Numeric Input Function (Expansion Card) 0 〇 F02.13 X10 Numeric Input Function (Expansion Card) 0 〇 F02.14 X11 Numeric Input Function (Expansion Card) 0 〇