sinee — 6.2 Function Parameter Table

EM500 Open-Loop Vector Control Inverter User Manual 93 F04.18 S Curve End Section Time at Deceleration 0.00 - System deceleration time/2 (F15.13=0) 0.0 - System deceleration time/2 (F15.13=1) 0 - System deceleration time/2 (F15.13=2) s 1.00 ● F04.19 Stop Mode 0: Ramp-To-Stop 1: Coast-to-Stop 0 〇 F04.20 DC Brake Start Frequency at Stop 0.00 - Maximum Frequency F00.16 Hz 0.00 〇 F04.21 DC Brake Current at Stop 0.0 - 150.0 (100.0= Motor Rated Current) % 100.0 〇 F04.22 DC Brake Time at Stop 0.00 - 30.00, Disabled at 0.00 s 0.00 〇 F04.23 DC Brake Field Weakening Time at Stop 0.00 - 30.00 s 0.50 〇 F04.24 Magnetic Flux Brake Gain 100 – 150 (100:

No Magnetic Flux Brake) 100 〇 F04.25 Not Used F04.26 Start Mode after Fault/Coast to Stop 0: Start as per Set Mode of F04.00 1: Rotation Speed Tracking Start 0 〇 F04.27 Terminal Start Command Reconfirmation 0: Not to Confirm 1: Confirm 0 〇 F04.28 Not Used F04.29 Zero speed frequency 0.00 – 5.00 Hz 0.25 ● F04.30 Initial Position Search after Power-on or Fault 0: Disabled 1: Enabled 0 ● F05 V/F Control Parameter Group F05.00 V/F Curve Setting 0: Straight Line V/F 1: Multi-Dot Polyline V/F 2: VF to the 1.3rd 3: VF to the 1.7th 4: Square V/F 5: VF Complete Split Mode (Ud=0, Uq=K*t=Split Voltage Source Voltage) 6: VF Half-Split Mode (Ud=0, 0 〇