EM600 High-Performance Vector Control Inverter User Manual PLC RUN 24V EM600 变频器 EM600 Inverter 运行 Run F/R RUN F/R f COM Forward/Reverse 正/反转 Output Frequency 输出 频率 -f 时间 Time (a) F00.03=0 2-Wire Sequence Wiring Diagram (b) F04.19=0, F00.03=0 Forward/Reverse Running Sequence PLC 正转 EM 600 Inverter 24V Forward RUN F/R RUN F/R EM600 变频器 RUN F/R f 输出 频率 f 输出 频率 Reverse 反转 Output Frequency COM -f 时间 -f 时间 Time (c) F00.03=1 2-Wire Sequence Wiring Diagram Running Sequence Figure 7-1 2-Wire Sequence (d) F04.19=0, F00.03=1 Forward/Reverse 3-Wire Sequence: F00.03=2:
Terminal RUN forward, Xi stop, F/R reverse RUN is a NO forward running button and F/R is a NO reverse running button; both of them are effective at pulse edge; Xi is a NC stop button and enabled at the level. Under running mode, pressing Xi can stop inverter. When stop mode is set as F04.19=0 Ramp-To-Stop, the logic diagram is shown in Figure 7-2 (b). Xi is a terminal among X1 - X7 and defined as 3-Wire Sequence Run/Stop Control. F00.03=3: Terminal RUN, Xi stop, Forward/Reverse (F/R) RUN is a NO running button, and will be on at pulse edge (F/R is on at level). F/R is a forward/reverse switching button (inverter forwards when F/R is disabled, and inverter reverses when F/R is enabled).
Xi is a NC stop button, and on at the level. When the stop mode is set as F04.19=0 Ramp-To-Stop, the logic sequence is shown in Figure 7-2(d).. 120 When selecting F00.03 start/stop option as 0 or 1, either pressing STOP or RESET using an external terminal stop command can stop inverter, even if terminal RUN is on. At this time, terminal RUN shall be disabled and then enabled, it can once again enter running state.