EM600 High-Performance Vector Control Inverter User Manual 139 Set Function Description Value 1 Run Terminal “RUN” If terminal control (F00.02=1) is selected as command source, inverter executes function F/R according to setting value of terminal control mode F00.03 under application that function terminal is enabled. (See F00.03 Function Code) 2 R/F If terminal control (F00.02=1) is selected as command source, inverter executes function F/R according to setting value of terminal control mode F00.03 under application that function terminal is enabled.
(See F00.03 Function Code) 3 3-Wire Sequence Stop Control If terminal control (F00.02=1) is selected as command source and terminal control mode is 3-wire sequence control (F00.03=2/3), inverter executes stop command under application that function terminal is enabled. (See F00.03 Function Code) 4 Forward JOG (FJOG) If command source is selected as terminal control (F00.02=1), inverter runs forward under application that FJOG function terminal is enabled. Inverter runs reversely, if RJOG function terminal is enabled. If both FJOG and RJOG are enabled at the same time, inverter will ramp to stop. See Figure Table 7-20. ★ If reverse is prohibited, FJOG is disabled.
5 Reverse JOG (FJOG) 6 UP If function terminal UP is enabled, frequency offset will increase at speed defined through F12.11; if function terminal DOWN is enabled, frequency offset will decrease at speed defined through F12.11. If the UP/DOWN offset clear terminal is enabled, frequency offset will be cleared; Setting source of final frequency source A = Setting frequency of frequency source A + UP/DOWN offset. ★ The UP/DOWN function is only enabled when main frequency source A is involved in setting; offset frequency can be viewed through F18.15. Terminal UP/DOWN has the same function as UP/DOWN on keypad.
7 DOWN 8 UP/DOWN Offset Clear 9 Coast-to-Stop Inverter will be blocked for output and coast to stop, if this function terminal is enabled during running. At this time, inverter is not conrolled by inverter 10 Fault Reset This terminal can be used for reset if inverter fails and the failure is remedied. It has the same functions as the reset button on keypad.