sinee — 7.3 F02 Group: Input Terminal Parameter

EM600 High-Performance Vector Control Inverter User Manual 141 Set Function Description Value 1 1 Preset Torque 3 (F13.05) 19 Acceleration/Deceleration Time Terminal 1 EM600 inverter has four groups of acceleration/deceleration terminals, each group having two input terminals for acceleration and deceleration. The setting of combined code of the 4 terminals, and relevant functions determines present acceleration/deceleration time. As stated in the following table: (0/1: present function terminal disabled/enabled). See function codes F15.03 - F15.13. 20 Acceleration/Deceleration Time Terminal 2 20 19 Acceleration/Deceleration Time 0 0 Group 1 (Acceleration Time: F00.14, Deceleration Time:

F00.15) 0 1 Group 2 (Acceleration Time: F15.03, Deceleration Time: F15.04) 1 0 Group 3 (Acceleration Time: F15.05, Deceleration Time: F15.06) 1 1 Group 4 (Acceleration Time: F15.07, Deceleration Time: F15.08) 21 Acceleration/Deceleration Prohibited If acceleration/decleration time terminal is disabled, command for acceleration/deceleration is prohibited and inverter’s output frequency remains the same. If inverter is under the overcurrent protection status, run inverter as per current limit mode. 22 Pause Operation Inverter ramps to stop, but all running parameters are memorized, for example PLC parameter, wobbulation parameter and PID parameter.

If terminal is disabled, inverter is reset to pre-stop running status. 23 External Fault Input Fault signal of external devices can be inputted through this terminal, so that inverter monitors and protects peripherals at fault. Upon receiving external fault signal, inverter displays “E14”, and coast to stop. 24 Switch Run Command to Keypad Priority rule is “24: Switch Run Command to Keypad” > “25: Switch Run Command to Communication” > “F00.02: Command Source” (see F00.02). 25 Switch Run Command to Communication 26 Frequency Source Switching Mainly used with F00.06, and applied to switching of frequency source. This terminal works only when F00.06=3 – 5. See F00.06 for details.

27 Clear Timed Run Time This terminal is defined through F16.05 and used to clear the time that inverter has run for (reset remaining time of timed run). See F16.05 for details. 28 Switch between Speed Control mode of inverter is selected by these two