sinee — 7.3 F02 Group: Input Terminal Parameter

EM600 High-Performance Vector Control Inverter User Manual 142 Set Function Description Value Control and Torque Control terminals and F13.00: if no. 28 terminal is enabled, control mode of inverter will switch between speed control and torque control; if no. 29 terminal is enabled, only speed control works. 29 Torque Control Disabled 30 Switch between Motor 1 and Motor 2 This terminal and F00.28 are used together to determine present set motor: if no.30 terminal is enabled, switching can be completed based upon F00.28. See F00.28 for details.

31 Simple PLC Status Reset (Start to Run with Preset Speed 1, Clear Run Time) When this terminal is enabled, simple PLC module will start to run again from the first preset speed. To further understand this function, user may view simple PLC description of F08. 32 Simple PLC Time Stop (Keep Running at Preset Speed) When this terminal is enabled, simple PLC module will keep running at present speed; after it is disabled, simple PLC module will continue running after present speed stage is compelted. 33 Zero Servo Command Under control mode F00.01=2, inverter enters zero servo status if terminal is enabled at stop status; it resets to pre-start status after this terminal is disabled.

34 Count Input (≤250Hz) Pulse input terminal with count function limits input pulse frequency to ≤250Hz. Only one terminal can be set with this function. See F16.03 - F16.04 for details. 35 High-Speed Count Input (≤100kHz, Only Enabled for X7) Pulse input terminal with count function limits input pulse frequency to ≤100kHz. Only one terminal can be set with this function. See F16.03 - F16.04 for details. 36 Counter Clear Clear counter that has counter function 37 Length Count Input (≤250Hz) Pulse input terminal with length count function limits input pulse frequency to ≤250 Hz. Only one terminal can be set with this function. See F16.01 - F16.02 for details.

38 High-Speed Length Count Input (≤100kHz, Only Enabled for X7) Pulse input terminal with count function limits input pulse frequency to ≤100kHz. This terminal is only enabled for X7 (i.e., F02.06=38). See F16.01 - F16.02 for details. 39 Length Clear A length clear terminal with length count function. 40 Pulse Input (≤100kHz, Only Enabled for X7) This is a pulse signal input terminal with input pulse frequency ≤100kHz. It is only enabled for X7. ★ This function can not be used for special functions (for example, count). This terminal is only used as setting equivalent to AI percentage. If F00.04=5, then set F02.06=40 and set the frequency pulse through terminal X7.

41 Process PID Stop When this terminal is enabled, then PID stops adjustment. At this time, the process maintains output. For more information, please refer to function code F09.18. 42 Process PID Integral Stop When this terminal is enabled, integral adjustment