EM600 High-Performance Vector Control Inverter User Manual Offset Output F02.29 100.0% 1 1 ( , ) X Y 100.00 0 F02.26 F02.28 Pulse Frequency/kHz 脉冲频率/ kHz F02.27 0 0 ( , ) X Y Figure 7-10 High-Speed Pulse Input Offset Curve When input pulse frequency changes fast or the system does not need to make a quick response to the input pulse, user may properly increase the filter time to stablize the system. -100.0% Analog input terminals AI1 - AI4 of EM600 inverter can be used as numeric terminals. User only needs to set them as 1. If terminal AI2 is used as a numeric terminal, i.e., F02.31=xx1x, its analog input and numeric logic are switched as follows:
When terminal input voltlage When terminal input voltlage >3V, the correesponding logic status is enable; When terminal input voltage falls between 1V and 3V, corresponding logic remains. Logic 1 0 Figure 7-11 Analog Input Terminal Volatage and Present Logic Status Relationship 0V 1V 3V Voltage 电压 Diagram If terminal is used as an analog input terminal, user may set the filter time and corresponding offset curve through F02.32 - F02.60. AI1 - AI4 can be set respectively. 147 Function Name of Parameter Description Unit Default Property Code Function Code F02.31 Analog Input Function Ones place: AI1 0: Not Used 1:
Numeric input (0 for less than 1V, 1 for over 3V, staying the same between 1V and 3V) Ten place: AI2 0: Not Used 1: Numeric input (the same as above) Hundreds place: AI3 0: Not Used 1: Numeric input (the same as above) 0000D 〇