sinee — 7.3 F02 Group: Input Terminal Parameter

EM600 High-Performance Vector Control Inverter User Manual F02.32 is used to select offset curve corresponding to each analog quantity input terminal and there are 4 groups of offset curves available for selection. Of the 4 groups of curves, curves 1 and 2 are of two-point offset type, and curves 3 and 4 are of four-point offset type; the minimum input voltage of curves 2 and 4 can be as low as -10V and meet requirements of AI4 input. After having selected offset curve, user can set corresponding function code to meet input requirements. It shall have the same meanings as HDI. See F02.26 - F02.29 for details.

User can properly adjust filter time according to analog input status and actual working condition. Please refer to actual result.

149 Function Code Name of Function Code Parameter Description Unit Default Property F02.44 Setting Corresponding to Input of Inflexion 1 of Curve 3 –100.0 - +100.0 % 25.0 ● F02.45 Input of Inflexion 2 of Curve 3 F02.43 - F02.47 V 7.50 ● F02.46 Setting Corresponding to Input of Inflexion 2 of Curve 3 –100.0 - +100.0 % 75.0 ● F02.47 Maximum Input of Curve 3 F02.45 - 10.00 V 9.90 ● F02.48 Setting Corresponding to Maximum Input of Curve 3 –100.0 - +100.0 % 100.0 ● F02.49 Minimum Input of Curve 4 -10.00 - F02.51 V -9.90 ● F02.50 Setting Corresponding to Minimum Input of Curve 4 –100.0 - +100.0 % -100.0 ● F02.51 Input of Inflexion 1 of Curve 4 F02.49 - F02.53 V -5.00 ● F02.52 Setting Corresponding to Input of Inflexion 1 of Curve 4 –100.0 - +100.0 % -50.0 ● F02.53 Input of Inflexion 2 of Curve 4 F02.51 - F02.55 V 5.00 ● F02.54 Setting Corresponding to Input of Inflexion 2 of Curve 4 –100.0 - +100.0 % 50.0 ● F02.55 Maximum Input of Curve 4 F02.53 - 10.00 V 9.90 ● F02.56 Setting Corresponding to Maximum Input of Curve 4 –100.0 - +100.0 % 100.0 ● F02.57 AI1 Filter Time 0.00 - 10.00 s 0.10 ● F02.58 AI2 Filter Time 0.00 - 10.00 s 0.10 ● F02.59 AI3 Filter Time 0.00 - 10.00 s 0.10 ● F02.60 AI4 Filter Time (Expansion Card) 0.00 - 10.00 s 0.10 ● Function Name of Function Code Parameter Unit Default Property Code Description F02.61 AD Sampling Hysteresis 2 - 50 2 〇