sinee — 7.4 F03 Group: Output Terminal Function Parameter

EM600 High-Performance Vector Control Inverter User Manual User can properly increase the function code, if input fluctuates greatly due to analog quantity input hysteresis, long input line or severe field interference. The principle of adjustment is to reduce adjustment as possible. 7.4 F03 Group: Output Terminal Function Parameter EM600 inverter has 2 multi-functional input terminals (Y1 and Y2) and 2 relay output terminals (R1 and R2). In addition, IO expansion card (EC-IO-A1) is optional and offers 1 multi-functional input output terminals (Y3). Y1 – Y3, R1 and R2 are 5 numeric multi-function output terminals.

By setting function codes F03.00 - F03.04, user can define the functions of output terminals respectively. For example, if F03.02=7, function of terminal R1 is “inverter fault”. If inverter is in fault status, R1 is in active output status; if inverter is normal status, R1 is in inactive output status. Specific functions available are shown in Table 7-6.

Table 7–6 Numeric Multi-Function Output Terminals 150 Function Name of Function Code Parameter Description Unit Default Property Code F03.00 Y1 Output Function See Table 7–6 Functions of Numeric Multi-Function Input Terminals 1 ○ F03.01 Y2 Output Function 3 ○ F03.02 R1 Output Function 7 ○ F03.03 R2 Output Function 8 ○ F03.04 Y3 Output Function (Expansion Card) 0 ○ Set Value Function Description 0 No Output Set “0: No Function” for an unused or fault terminal to prevent false output. 1 Inverter Running (RUN) When inverter is in slave running, slave stop, JOG running or JOG stop status, present output is active; in other status, present output is inactive.

2 Frequency Reach Range (FAR) When inverter is in running status and absolute value of “output frequency – set frequency” ≤ frequency reach detection width (F15.20), present output is active; when inverter is not in running status or absolute vaule of “output frequency – set frequency” > frequency reach range (F15.20), present output is inactive. See function code F15.20 for details.

3 Output Frequency Detection Range FDT1 When inverter is in running status, and absolute value of output frequency > output frequency detection range FDT1 (F15.21), then present output is active; when inverter is not in running status, or absolute value of output frequency ≤ output frequency detection range FDT1 (F15.21) - hysteresis FDT1 (F15.22), present output is inactive; for other status, present output status remains unchanged. See the Function Codes F15.21 and F15.22 for details.

4 Output Frequency Detection Range FDT2 When inverter is in running status, and absolute value of output frequency > output frequency detection range FDT1 (F15.23), then present output is active; when inverter is not