EM600 High-Performance Vector Control Inverter User Manual 151 Set Function Description Value in running status, or absolute value of output frequency ≤ output frequency detection range FDT2 (F15.23) - hysteresis FDT1 (F15.24), present output is inactive; for other status, present output status remains unchanged. See function codes F15.23 and F15.24 for details. 5 Reverse Running (REV) When running direction and acceleration/deceleration status of inverter are reverse acceleration, reverse deceleration or reverse constant speed, present output is active. 6 JOG Running When inverter is in JOG running or JOG stop status, present output is active.
7 Inverter Fault When inverter is in fault status, present output is active; in other status, present output is inactive. 8 Inverter Ready When inverter is ready for running after it is powered on and finishes initialization without any fault, present output is active. 9 Upper Limit Frequency Reach When inverter is in JOG or slave running status, output frequency (F18.00) ≥ upper limit frequency (F00.17||F00.18) and set frequency (F18.01) ≥ upper limit frequency (F00.17||F00.18), present output is active. Otherwise, present output is inactive.
10 Lower Limit Frequency Reach When inverter is in JOG or slave running status, output frequency (F18.00) ≤ lower limit frequency (F00.19) and set frequency (F18.01) ≤ lower limit frequency (F00.19), present output is active. Otherwise, present output is inactive. 11 Current Limit Reach When output current (F18.06) ≥ current limit level (F07.12), present output is active. When output current (F18.06) ≤ current limit level (F07.12) -5.0%, present output is inactive. When the voltage is the intermediate value, present output status remains the same. 12 Overvoltage Stall Voltage Reach When output voltage (F18.07) ≥ Overvoltage stall control voltage (F07.07), present output is active.
When output voltage (F18.07) ≤ Overvoltage stall control voltage (F07.07) -10V, present output is inactive. When the voltage is the intermediate value, present output status remains the same. 13 Simple PLC Cycle Finished When simple PLC running mode is “stop after single running” (F18.15=0), inverter stops after single running, and present output is active; when simple PLC running mode is “stop after limited times of running” (F18.15=1), inverter stops after running as per F08.16, present output is active; otherwise (run again, simple PLC status reset, etc.), present output is inactive.
14 Set Count Value Reach When input pulse count value (F18.34) ≥ set count value (F16.03), present output is active, otherwise output is