EM600 High-Performance Vector Control Inverter User Manual 152 Set Function Description Value inactive. See function codes F16.03 - F16.04 for details. 15 Designated Count Value Reach When input pulse count value (F18.34) ≥designated count value (F16.04), present output is active, otherwise output is inactive. See function codes F16.03 - F16.04 for details. 16 Length Reach When the input pulse conversion value (F18.34) ≥ set count value (F16.01), present output is active, otherwise output is inactive. See function codes F16.01 - F16.02 for details. 17 Motor Overload Pre-alarming When present motor current ≥ motor pre-alarming factor (F07.02), present output is active.
Otherwise, output is inactive. 18 Inverter Overheating Pre-Alarming When inverter temperature >= overheat spot -25℃, the pre-alarming output is active, otherwise the pre-alarming output is inactive. 19 PID Feedback Upper Limit Reach If PID feedback (F18.17) ≥ upper limit of PID output (F09.16) when inverter is running, present output is active. Otherwise, present output is inactive. 20 PID Feedback Lower Limit Reach If PID feedback (F18.17) ≤ lower limit of PID output (F09.17) when inverter is running, present output is active. Otherwise, present output is inactive.
21 Analog Quantity Level Detection ADT1 If selected analog quantity channel input ≥ analog quantity level detection (F15.26/28), corresponding output is active; if selected analog quantity channel input ≤ analog quantity level detection (F15.26/28) – hysteresis (F15.27/29), present output is inactive; When inverter is in other status except the two above, present output status remains the same.See F15.25 - F15.29 for details. 22 Analog Quantity Level Detection ADT2 23 Zero Servo If inverter is in zero servo control mode, present output is active. Otherwise, present output is inactive.
24 Undervoltage Status When DC bus voltage (F18.08) ≤ undervoltage stall control voltage (F07.08), present output is active. When DC bus voltage (F18.08) ≥ judgment operation voltage at power failure ending (F07.09), and maintenance time ≥ judgment delay time at power failure ending (F07.10), present output is inactive. 25 Motor Overload Pre-alarming When present motor temperature (F18.38) ≥ motor overheating pre-alarming threshold (F07.05), present output is active. Otherwise, output is inactive. See F07.03 - F07.05 for details. 26 Set Time Reach When timed run time is reached, present output is active. Otherwise, present output is inactive.
27 Run at Zero Speed When inverter is in JOG or slave running status, and output frequency (F18.00) ≤ zero servo start frequency (F04.29), present output is active. Otherwise, present output is inactive. 28 – 35 Not Used