EM600 High-Performance Vector Control Inverter User Manual If output current is lower than offload detection level (F07.22) and this status continues for offload detection time (F07.23) when offload detection protection is enabled (F07.21=1) and inverter is in running mode and not in DC brake, then inverter gives an offload protection fault ( E26 ) report and stops as the offload protection setting (F07.24). If F07.26 is set as 0, the overspeed protection is disabled.
If F07.26 is not set as 0, inverter gives an alarm for motor overspeed protection fault ( E25 ) as long as load speed is higher than motor overspeed detection level (F07.25) and this status continues for motor overspeed detection (F07.26). Motor overspeed detection will be triggered only when inverter is running or in JOG running status in FVC control mode (F00.01=2). F07.27=0: AVR is disabled. F07.27=1: AVR is enabled. The output of inverter is stable when there is voltage fluctuation. F07.28=0: stalling fault detect is disabled. F07.28 isn’t 0 and the stalling time is more than F07.28 there is fault E20. 7.9 F08 Group: Preset Speed and Simple PLC Parameter 178 1:
Stop as per the Set Stop Mode Function Name of Function Parameter Description Unit Default Property Code Code F07.25 Motor Overspeed Detection Level 0.0 - 50.0 (reference frequency is Maximum Frequency F00.16) % 20.0 ● F07.26 Motor Overspeed Detection Time 0.0 - 60.0, 0.0: cancel motor overspeed protection s 1.0 ● Function Name of Function Parameter Description Unit Default Property Code Code F07.27 AVR 0: Disabled 1:
Enabled 1 〇 Function Name of Function Parameter Description Unit Default Property Code Code F07.28 Stalling Fault Detection Time 0.0 – 6000.0 (0.0 stalling fault is disabled) s 60.0 〇 Function Name of Function Parameter Description Unit Default Property Code Code F08.00 Preset Speed 1 0.00 - Maximum Frequency F00.16 Hz 0.00 ● F08.01 Preset Speed 2 0.00 - Maximum Frequency F00.16 Hz 5.00 ●