sinee — 7.8 F07 Group: Fault Protection Parameter

EM600 High-Performance Vector Control Inverter User Manual Fault retry function can be used to prevent the impact of an accident upon normal system operation. It is only valid for some faults listed by F07.18. When fault retry function is enabled, a fault will cause inverter to start a fault retry, i.e., fault reset. Whether a fault status is outputted by numeric output terminal shall be set through F07.15.

If the fault is still detected subsequent to fault retry, continue with the fault retry until set fault retry times (F07.14) are reached; if the fault is still detected after the fault retry times, an alarm will be given correspondingly; if the fault does not occur again in several following retries, the fault retry succeeds and inverter continues to work normally. After fault retry succeeds, fault retry times will be cleared if no fault occurs in the recovery time of fault retry times (F07.17), and fault retry still starts from 0 times when a fault occurs in the future; a fault retry time will be counted based upon last fault retry count, if the fault still occurs in this retry.

These function codes can be used to set inverter action mode when some faults occur. If any of them is set as 0, inverter coasts to stop; if any of them is set as 1, inverter stops as per set stop mode (F04.19). Such function codes are under bit operation. Set corresponding position as 0 or 1 while setting them. See the table below. Table 7-9 Action Bit at Fault For example, user only needs to set the first bit of OlP and the third bit of E13 as 1, in order to set OlP and E13 as stop as per set stop mode (F04.19) in case of a fault. 177 F07.17 Recovery Time of Fault Retry Times 0.01 - 30.00 s 10.00 ● F07.18 Fault Retry Ilp HOU HOC SlU SOU SOC **0 00000 〇 0: Permitted 1:

Not Permitted Name of Function Function Parameter Description Unit Default Property Code Code F07.19 Action 1 at Fault E21 E16 E15 E14 E13 E12 Olp Ilp 000 00000 〇 0: Coast to Stop 1: Stop as per the Set Stop Mode F07.20 Action 2 at Fault E28 E27 E25 E23 *0000 〇 0: Coast to Stop 1: Stop as per the Set Stop Mode F07.19 E21 E16 E15 E14 E13 E12 Olp Ilp F07.20 * * * * E28 E27 E25 E23 Corresponding Bit 7 6 5 4 3 2 1 0 Set Value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 Function Name of Function Code Parameter Description Unit Default Property Code F07.21 Offload Protection 0: Disabled 1:

Enabled 0 ● F07.22 Offload Detection Level 0.0 - 100.0 % 20.0 ● F07.23 Load Detection Time 0.0 - 60.0 s 1.0 ● F07.24 Offload Protection 0: Coast to Stop 1 〇