sinee — 7.8 F07 Group: Fault Protection Parameter

EM600 High-Performance Vector Control Inverter User Manual F07.11=0: Disabled Currnt limit does not work. F07.11=1 : Limit Mode 1 F07.11=2 : Limit Mode 2 During operation, if output current reaches to current limit level F07.12 and current limit control is effective, then the system will automatically start current limit: reducing output frequency to restrain output current from going up, and inverter will quit from over current state. Inverter will return to previous running status, when output current reduces to a value below current limit action level. Current limit action procedure is shown in Figure 7-25.

Output Frequency (Hz) Time (S) Output Current (%) Time (S) Figure 7-25 Current Limit Action Procedure F07.12 is used to set the action conditions for enabling current limit. If inverter output current exceeds set value of this function code, the current limit function starts to act, so as to control output current at a level not greater than the current limit. Current limit only works for inverter under V/F control mode. It's recommended to use this function for occasions of large inertia, fan type load, and the occasion “one inverter shared by multiple motors”. F07.13=0: Disabled Rapid current limit does not work. F07.13=1: Enabled The rapid current limit can reduce the overcurrent fault.

176 Level Current) Function Name of Function Parameter Description Unit Default Property Code Code F07.13 Rapid Current Limit 0: Disabled 1: Enabled 0 〇 Function Name of Function Parameter Description Unit Default Property Code Code F07.14 Fault Retry Times 0 – 20, 0: Fault Retry Disabled 0 〇 F07.15 Numeric Output Action at Fault Retry 0: Disabled 1: Enabled 0 〇 F07.16 Fault Retry Interval 0.01 - 30.00 s 0.50 ●