sinee — 7.8 F07 Group: Fault Protection Parameter

EM600 High-Performance Vector Control Inverter User Manual When bus voltage is lower than the value set through F07.08, inverter stops after decelerating to zero, and gives an alarm for stable undervoltage fault (SIU). F07.06=2: Overvoltage Stall, Enabled If overvoltage stall is enabled, stall voltage is set by F07.07. DC bus overvoltage is generally caused by deceleration, because at the time of deceleration, DC bus voltage rises due to energy feedback. When the DC bus voltage is higher than the overvoltage threshold:

If the overvoltage stall is enabled (F07.06=2/3) when the DC bus voltage is higher than the overvoltage threshold, inverter stops the deceleration and keeps output frequency unchanged; as a result, energy feedback stops; until DC busbar voltage backs to normal, inverter starts deceleration again. During deceleration, overvoltage stall protection process is shown in Figure 7-24. Overvoltage stall DC Bus Voltage Overvoltage stall ineffective voltage Output frequency Regenerative overvoltage t Figure 7-24 Overvoltage Stall Protection F07.06=3: Overvoltage Stall and Undervoltage Stall, Enabled Inverter is protected for both overvoltage stall and undervoltage stall.

If bus voltage is lower than the value set through F07.08 (Undervoltage Stall Control Voltage), inverter will enter power failure status. If bus voltage is greater than F07.09 (Judgment Operation Voltage at Power Failure Ending), which lasts for the time set by F07.10 (Judgment Delay Time at Power Failure Ending), then inverter returns to the normal status.

175 Function Name of Function Code Parameter Description Unit Default Property Code F07.09 Judgment Operation Voltage at Power Failure Ending Undervoltage Stall Control Voltage - 100.0 % 86.0 ● F07.10 Judgment Delay Time at Power Failure Ending 0.00 - 100.00 s 5.00 ● Function Name of Parameter Description Code Function Code Unit Default Property F07.11 Current Limit Control 0: Disabled 1: Limit Mode 1 2: Limit Mode 2 2 〇 F07.12 Current Limit 20.0 - 180.0 (100.0= Inverter Rated % 150.0 ●