EM600 High-Performance Vector Control Inverter User Manual If the accumulative output current of inverter is greater than the product of the overload inverse-time curve and F07.02, the multi-function numeric Do of inverter outputs “17: motor overload pre-alarm” ON signal. Default inverter is “no motor temperature protection”. To enable this protection, please confirm that present motor has a temperature sensor and transmits the temperature signal to analog input terminal 4 (AI4, equipped with our IO card EC-IO-A1), and set temperature sensor type (F07.03) to start motor overheating protection.
User can view present motor temperature through function code F18.38; if motor temperature is greater than motor overheating pre-alarm threshold (F07.05), numeric output terminal “25: Motor Overload Pre-alarming” is enabled and this signal is used for instruction; if motor temperature is greater than motor overheating protection threshold (F07.04), inverter will give an alarm about motor overheating fault ( E12 ) and start corresponding protection action. ★ Motor overheating fault ( E12 ) can not be reset immediately until motor temperature drops to a value far below the protection threshold. F07.06=0:
Disabled Overvoltage stall disabled; it’s not recommended to set F07.06 as 0, if there is no external braking unit. Undervoltage stall disabled; F07.06=1: Undervoltage Stall, Enabled 174 Function Parameter Name of Function Code Unit Default Property Code Description F07.03 Motor Temperature Sensor Type 0: No Temperature Sensor 1: PT100 2: PT1000 0 ● F07.04 Motor Overheating Protection Threshold 0 - 200 ℃ 110 ● F07.05 Motor Overheating Pre-Alarming Threshold 0 - 200 ℃ 90 ● Function Name of Function Parameter Description Unit Default Property Code Code F07.06 Bus Voltage Control Options 0: Disabled 1: Undervoltage Stall, Enabled 2: Overvoltage Stall, Enabled 3:
Overvoltage Stall and Undervoltage Stall, Enabled 2 〇 F07.07 Overvoltage Stall Control Voltage 110.0 - 150.0 (380V, 100.0=537V) % 128.5 ● F07.08 Undervoltage Stall Control Voltage 60.0 - Judgment Operation Voltage at Power Failure Ending (100.0= Standard Bus Voltage) % 76.0 ●