EM600 High-Performance Vector Control Inverter User Manual At low frequency range (output frequency F06.29; at high frequency range (output frequency > F06.32), injection current is determined through F06.33. User may adjust gain and integral time with regulator to achieve better effect. Generally, user may use the default value. Please do not adjust it if you are not a professional. 7.8 F07 Group: Fault Protection Parameter Bit setting value=0: After detecting fault corresponding to the bit, inverter will stop output and enter fault status. Bit setting value=1: After detecting fault corresponding to the bit, inverter will not enable protection and remains the previous status.
This code is bit operation. Only corresponding bit has to be set as 0 or 1. See the table below. Figure 7-8 Fault Protection Shielding Bit For instance: for shielded IlP protection, only the first bit corresponding to IlP needs to be set as 1, i.e., F07.00=00000010. To shield OlP and E13 , set bit 0 of OlP and bit 5 of E13 to 1, Namely, F07.00=xx1 xxxx1. Please do not shield any protection function unless specially required. Otherwise, inverter may be damaged due to no protection in case of a fault. Inverse-time curve for motor overload protection:
200%Ч(F07.01)ЧMotor Rated Current, for 1 seconds continuously, an alarm is given for motor overload fault ( E13 ); 150%Ч(F07.01)ЧMotor Rated Current, for 15 minutes continuously, an alarm is given for motor overload. User must set F07.01 according to motor’s actual overload capacity. Excessive F07.01 value can easily pose a hazard of motor overheating without an alarm. F07.02 pre-alarm factor is used to determine what degree prior to motor overload protection will trigger an alarm. The higher this factor is, the smaller the advance time of the pre-alarm will be.
173 Name of Function Function Parameter Description Unit Default Property Code Code F07.00 Protection Shield - E22 E13 SlU SOU SOC IlP 000 00000 〇 0: Valid Protection 1: Protection Shielded Protection Code E22 E13 SlU SOU SOC IlP OlP Corresponding Bit 6 5 4 3 2 1 0 Set Value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 Function Name of Function Code Parameter Description Unit Default Property Code F07.01 Motor Overload Protection Gain 0.20 - 10.00 1.00 ● F07.02 Motor Overload Pre-Alarming Factor 50 - 100 % 80 ●