EM600 High-Performance Vector Control Inverter User Manual 8 Motor Parameter Autotuning 8.1 Motor Parameter Autotuning When inverter is in vector control, motor parameter autotuning is required. However, if not, parameter autotuning is also suggested for acquiring higher control precision at initial operation. EM600 provides the function of motor parameter autotuning. After the function is enabled, inverter autotunes connected motor parameters and saves parameter values to internal memory. For definitions of motor parameters, please refer to Figure 8-1 for 3-phase induction motor parameters.
R1 L1-Lm R2 L2-Lm I1 I2 U1 I0 Lm (1-s)/s*R2 Figure 8-1 Equivalent Circuit of 3-Phase Induction Motor In the figure, meanings of R1, R2, L1, L2, Lm and I0: Stator resistor, rotor resistor, stator inductance, rotor inductance, stator & rotor mutual inductance, and idling excitation current respectively; leakage inductance Ls=L-Lm. 8.2 Precautions Before Autotuning Autotuning is a process of autotuning motor parameters. EM600 can autotune motor parameters in 2 modes: stationary autotuning and rotational autotuning. Stationary autotuning is applied to the occasions when motor can not be disconnected from load, but inverter can obtain motor parameters.
Rotational autotuning is applied to the occasions when motor can be disconnected from load. Before autotuning, motor shall be disconnected from load. Never perform rotational autotuning for a motor with load. Make sure that motor is in stop status before autotuning; otherwise, autotuning can not be performed normally. Autotuning is only enabled when inverter is in keypad control mode (F00.02=0) . To ensure normal autotuning, set all motor parameters as per values listed on motor nameplate correctly: for open loop control F01.00: Motor model, F01.01: Motor rated power, F01.02: Motor rated voltage, F01.03: Motor rated current, F01.04: Motor rated frequency, F01.05:
Motor rated speed, F01.06: Motor wiring method and F01.07: Motor rated power factor. For closed loop control extra parameters should be set: F01.24 (Encoder Type) and F01.25 (Encoder Resolution). Based on rated power of inverter, match inverter with applicable Y-series motor, and defaults of motor can meet most of needs. To ensure control performance, motor and inverter shall match in terms of power rating. Usually, power rating of motor is only allowed to be one level lower than that of inverter. After autotuning finishes normally, setting values of F01.09 - F01.13and F01.19 – 234