EM600 High-Performance Vector Control Inverter User Manual F01.22 will be updated and auto-saved. When F12.14=1 reset defaults, parameters of F01.00 - F01.13 and F01.19 – F01.22 remain unchanged. 8.3 Steps of Autotuning In parameter setting status, set F00.2=0, and disconnect motor from load. Set all motor parameters as per values listed on nameplate correctly: F01.00: Motor model, F01.01: Motor rated power, F01.02: Motor rated voltage, F01.03: Motor rated current, F01.04: Motor rated frequency, F01.05: Motor rated speed, F01.06: Motor wiring method and F01.07: Motor rated power factor.
Asynchronus motor autotuning By setting F01.34=1, and pressing RUN , inverter starts stationary autotuning for motor. Or by setting F01.34=2, and pressing RUN , inverter starts rotational autotuning for motor. Synchronus motor autotuning By setting F01.34=11, and pressing RUN , inverter starts stationary autotuning for motor. Or by setting F01.34=12, and pressing RUN , inverter starts rotational autotuning for motor. Or by setting F01.34=13, and pressing RUN , inverter starts rotational autotuning for motor’s encoder. It takes about 2 minutes to complete autotuning and, afterwards, keypad returns to initial power-on status.
By pressing , inverter will return to parameter setting status. If autotuning fails, inverter will display “ E24 ” parameter autotuning fault. By pressing pressing in autotuning, it will display “ E24 ” parameter autotuning fault. By STOP RESET , inverter will return to parameter setting status. 235 STOP RESET STOP RESET