sinee — 9.1 Faults

EM600 High-Performance Vector Control Inverter User Manual 9 Troubleshooting 9.1 Faults When something abnormal happens to inverter, keypad will display corresponding fault code and parameter; the fault relay is on, the fault output terminal is on, inverter output stops. If motor is still running when a fault occurs, it will ramp to stop or coast to stop. For EM600 faults and countermeasures, see Table 9-1. Table 9-1 EM600 Faults and Troubleshooting 236 Fault Fault type Cause Troubleshooting Code SC Short Circuit/EMC Fault 1. Short circuit between output phase and ground 2. Short circuit between phases 3. Short circuit of external brake resistor 4.

Acceleration/deceleration time is too short 5. Power module is damaged 6. Field interference 1. Check if there is any short circuit phenomenon in wiring. 2. Extend acceleration/deceleration time.Investigate causes and reset after taking appropriate measures. 3. Seek for technical support. HOC Instantaneous Overcurrent 1. Short circuit between inverter output phases, or between output phase and ground. 2. Acceleration/deceleration time is too short. 3. Under V/F control mode, V/F curve has been set irrationally. 4. Motor is running when inverter starts. 4. Motor exceeds inverter capacity or load is too heavy. 5. IGBT damaged (HOC). 1. Check if there is any short circuit phenomenon in wiring.

2. Extend acceleration/deceleration time. 3. Set V/F curve rationally. 4. Enable revolution track or start DC brake. 5. Replace with appropriate motor or inverter. SOC Stable Overcurrent HOU Instantaneous Overvoltage 1. Deceleration time is too short and regenerated energy is too large. 2. Input voltage is too high. 1. Extend deceleration time. 2. Select appropriate braking unit/braking resistor. 3. Lower input voltage to the specified range. SOU Stable Overvoltage SlU Stable Undervoltage 1. Input voltage phase loss. 2. Wiring terminals of input voltage are loosened. 3. Input voltage drops too much.. 4. Aging of switch contact on input power supply. 1. Check input voltage and its wiring.

2. Tighten screws of input wiring terminal. 3. Check air switch and contactor. IlP Input Phase Loss 1. Input voltage phase loss. 1. Check input voltage. 2. Check input voltage wiring.