sinee — 9.1 Faults

EM600 High-Performance Vector Control Inverter User Manual 237 Fault Fault type Cause Troubleshooting Code 3. Check whether connection terminals are loosened. OlP Output Phase Loss 1. Phase loss of U, V and W. 1. Check connection between inverter and motor. 2. Check whether motor winding is disconnected; 3. Check whether output terminals are loosened. Ol Inverter Overload 1. Acceleration/deceleration time is too short. 2. Under V/F control mode, V/F curve has been set irrationally. 3. Load is too heavy. 1. Extend acceleration/deceleration time. 2. Set V/F curve rationally. 3. Replace inverter with another one that matches with load. OH Radiator overheating 1. Ambient temperature is too high.

2. Inverter is in poor ventilation. 3. Cooling fan fault. 1. Running applications of inverter shall comply with specification requirements. 2. Improve ventilation environment and check whether air duct is blocked. 3. Replace cooling fan. E11 Parameter Setting Conflict 1. Parameter setting logic conflict. 1. Check whether parameters set prior to fault are unreasonable. E12 Motor Overheating 1. Detection of motor temperature is greater than the threshold 2. Motor temperature sensor is broken. 3. Ambient temperature is too high 4. The load is too heavy 1. Check motor temperature threshold. 2. Check motor temperature sensor 3. Improve heat dissipation of the motor 4.

Choose the proper motor E13 Motor Overload 1. Acceleration/deceleration time is too short. 2. Under V/F control mode, V/F curve has been set irrationally. 3. Load is too heavy. 1. Extend acceleration/deceleration time. 2. Set V/F curve rationally. 3. Replace proper motor matching load. E14 External Fault 1. Peripheral fault terminal acts. 1. Check peripherals. E15 Inverter EEPROM Fault 1. Interference results in reading and writing errors of EEPROM. 2. EEPROM damaged. 1. Press STOP/RESET to reset and then try it again. 2. Seek for technical support.