sinee — 9.1 Faults

EM600 High-Performance Vector Control Inverter User Manual 238 Fault Fault type Cause Troubleshooting Code E16 Communication Fault 1. the communication timeout is enabled for discontinuous communication system 2. SCI communication failure 1. Set F10.03 to 0.0 for discontinuous communication system 2. Check whether the communication cable is disconnected. 3. Adjust the communication overtime (F10.03). E17 Inverter Temperature Sensor Failure 1. Inverter temperature sensor is off or short-circuited. 1. Check whether temperature sensor of inverter is properly wired. 2. Seek for technical support. E18 Soft Start Relay Unclosed 1. The grid is interrupted. 2. Input voltage phase loss. 3.

Wiring terminals of input voltage are loosened. 4. Input voltage drops too much. 5. Aging of switch contact on input power supply. 1. interruption of power supply should be done after the inverter stopped or reset the fault. 2. Check the input voltage and its wiring. 3. Tighten screws of input wiring terminal. 4. Check air switch and contactor. E19 Current Detection Circuit Fault 1. Detection circuit of drive board or control board is damaged. 1. Seek for technical support. E20 Stall Fault 1. The set deceleration time is excessively short. 2. Energy consumption brake fault at coast-to-stop. 1. Increase set deceleration time. 2. Check energy consumption brake status.

E21 PID Feedback Disconnection 1. PID feedback is higher than upper limit (F09.24) or lower than lower limit (F09.25), depending upon types of sensors. 1. Check whether the feedback line falls off. 2. Check whether the sensor works abnormally. 3. Adjust the feedback disconnection detection value to a reasonable level. E22 Encoder Fault 1. Encoder and PG card are not properly connected. 2. PG card is not installed properly. 3. PG card type is wrong or F01.24 (Encoder Type) is wrong. 4. Encoder is damaged. 5. Interference on site. 1. Check whether PG card and encoder are wired correctly. 2. Check whether PG card is properly inserted. 3. Please check PG card type or F01.24 (Encoder Type). 4.

Replace encoder. 5. Adding ferrite cores to inverter output power cables