EM600 High-Performance Vector Control Inverter User Manual 10 Maintenance and Inspection 10.1 Routine Maintenance and Inspection of Inverter Changes of working environment of inverter, such as temperature, humidity, smog and dust, as well as aging of inner parts, can cause various inverter faults. Therefore, routine inspection and regular maintenance shall be performed during storage and use. Before using inverter, user shall check if components are broken or screws are loose during transport. While using inverter, user shall regularly clean dust and check whether screws are loosened.
If inverter is left unused for a long term, user is recommended to power on inverter every half year during storage. Every time, inverter shall be powered on for half an hour. This will prevent electronic device from invalidation. Keep inverter away from heavy humidity and metal particles. If necessary, put it in an electric cabinet or a small room with protective measures. When inverter is in normal running, please check items below: Whether motor sounds abnormally or vibrates. Whether inverter and motor are overheated abnormally. Whether ambient temperature is too high. Whether output current value is normal. Whether cooling fan of inverter runs normally.
According to service applications, clients shall regularly inspect inverter for clearing faults and potential safety hazards. Cut off power supply before checking, and start checking after keypad LED goes out. Items to be checked are shown in Table 10-1. Table 10-1 Items for Routine Check In order to make inverter operate normally, regular maintenance and change must be performed for the purpose of service life of inner components of inverter. Service lives of inverter components vary with service environment and applications. In Table 10-2, replacement terms of interver components are just for user reference.
243 Items Inspection content Countermeasures Screws of main circuit terminal and control circuit terminal Whether screws are loosened. Tighten screws with a screwdriver. Cooling fin Whether there is dust or foreign object. Clean up dust and foreign objects with dry-compressed air of 4-6 kg/cm2 pressure. PCB Cooling fan Whether there is abnormal sound or vibration. Whether accumulated run time has reached to 20,000 hours. Replace cooling fan. Power module Whether there is dust. Clean up dust and foreign objects with dry-compressed air of 4-6 kg/cm2 pressure. Electrolytic Capacitor If there is color change, foreign odor or blister. Replace electrolytic capacitor.