EM600 High-Performance Vector Control Inverter User Manual 9.1.5 Electromagnetic Interference (EMI) and Radio Frequency Interference (RFI) When inverter runs in high frequency switch status, it will generate EMI and RFI on the control devices. Take following countermeasures: Lower carrier frequency of inverter (F00.23). Install noise filter on the input side of inverter. Install noise filter on the output side of inverter. Shield cable with metal tube, and place inverter in a metal case. Inverter and motor must be grounded reliably. Main circuit and control circuit shall be wired separately. Control circuit shall adopt shielded wire, and see Chapter 3 for wiring.
9.1.6 Leakage Current Circuit Breaker for Leakage Protection When inverter runs, leakage current circuit breaker is triggered for leakage protection. Inverter outputs high-frequency PWM signal, which generates high-frequency leakage current. Please select leakage circuit breaker with trigger current ≥ 30mA. For regular circuit breaker, then trigger current ≥ 200mA and active time at 0.1S or above. 9.1.7 Mechanical Vibration Inherent frequency of mechanical system resonates with carrier frequency of inverter. Motor has no problem, but sharp noises generated by the mechanical system resonate between inherent frequency of mechanical system and carrier frequency of inverter.
Please adjust carrier frequency F0-14 to avoid resonant frequency. Inherent frequency of mechanical system resonates with output frequency of inverter. Inherent frequency of mechanical system resonates with output frequency of inverter. Please use oscillation suppression function (F05.13) or install vibration-proof rubber at motor bottom plate and take any other vibration-proof measures. PID Control Oscillation P, Ti and Td of PID controller do not match in setting properly. Reset PID parameters. 9.1.8 Inverter Stops Output While Motor Still Rotates Insufficient DC Brake at Stop DC brake torque at stop is too small. Please increase set value of DC brake current at stop (F04.21).
DC brake time at stop is too short. Please increase DC brake time at stop (F04.22). Generally speaking, increase DC brake current at stop first. 9.1.9 Output Frequency Not As Per the Set Frequency Set frequency exceeds upper limit frequency. If set frequency exceeds set value of upper limit frequency, then output frequency shall be upper limit frequency. Reset set frequency within upper limit frequency; or check whether F00.16, F00.17 and F00.18 are appropriate. 242