EM600 High-Performance Vector Control Inverter User Manual 9.1.1 Parameters Unavailable for Setting When pressing , parameter display remains unchanged. Some parameters can only be edited when inverter stops. F12.02 is set by 1 or 2, parameter locking will happen, please set F12.02 as 0. Or setting the user password will appear the same situation. and 9.1.2 Abnormal Motor Operation After pressing RUN , motor does not run. Start/Stop is in terminal control mode: Check F00.02 setting. Coast-to-stop terminals FRS is connected to COM: Disconnect FRS from COM. When terminal (Run Command Switched to Terminal) is on and run command is only in terminal control mode: Switch terminal off.
Status combination of run command input is in terminal control mode: Change it to keypad control mode. Setting reference input frequency= 0: Increase reference input frequency. Power supply is abnormal or control circuit fails. When control terminals RUN and F/R are ON, motor does not run. External terminal start/stop setting is disabled: Check setting of F00.02. Coast-to-stop terminal FRS=ON: Switch FRS=OFF. Control switch is disabled: Check control switch. Setting reference input frequency= 0: Increase reference input frequency. Motor can only run in one direction. Reverse prohibited: When F0-24=1, inverter reverse is prohibited.
Motor reverses Output phase sequence of inverter is not identical to that of motor input: When power is off, running direction of motor can be changed by switching any of the two connection wires on the output side of inverter. 9.1.3 Excessively Long Acceleration Time Excessively low setting of current limit When current limit is enabled, if inverter output current reaches its set current limit, then output frequency will remain unchanged in acceleration, and it will rise continuously only until output current is lower than set current limit. In this case, motor acceleration time is longer than set time. Check if set current limit of inverter is excessively low.
If set acceleration time is too long, confirm its parameters. 9.1.4 Excessively Long Deceleration Time When energy consumption brake is enabled, Brake resistance value is too big and energy consumption brake power is too small, so deceleration time is prolonged. Set value of brake duty ratio (F15.32) is too small, and deceleration time is prolonged. Please increase set value of brake duty ratio. If set acceleration time is too long, confirm its parameters. When overvoltage stall protection is enabled, Overvoltage stall protection is enabled, when DC bus voltage exceeds overvoltage stall voltage (F07.07), output frequency remains unchanged.
When DC bus voltage is lower than F07.07, output frequency drops continuously and therefore deceleration time is prolonged. If set acceleration time is too long, confirm its parameters. 241