sinee — 11.1 Braking Resistor

EM600 High-Performance Vector Control Inverter User Manual 11 Options 11.1 Braking Resistor If motor speed falls too fast or motor load shakes too frequently during inverter running, its electric potential energy will charge inner capacitor through inverter in a reverse way, leading to voltage pump up at both ends of power module, which easily damages inverter. Internal control of inverter can suppress this situation based on load condition and when braking feature can not meet user demands, external braking resistor is required to release energy timely. External braking resistor functions for energy consumption brake, which will dissipate all energy to power braking resistor.

So, select reasonable and effective power and resistance for braking resistor. The power of braking resistor is according to the following formula. D - Braking frequency (estimated value) Pb (The power of braking resistor) = P (the power of inverter) * D (braking frequency) Normally braking D = 10% Occasionally braking D = 5% Elevator braking D=10% ~ 15% Lifting braking for height more than 100m D= 50% ~ 60 The table below for the EM500 series inverter is recommended rated power of braking resistor which is for reference only (D=10% ~ 20%). If braking frequency is lager the power of braking resistance should be larger. ★ The cable listed above refers to outgoing line of individual resistor.

When resistor is 245 Motor Resistance Resistor power Cable connected to Inverter model (kW) (Ω) (W) the resistor (mm2) EM500-0R7G/1R5P-1B/2B/3B 0.75 ≧360 ≧200 1 EM500-1R5G/2R2P-1B/2B/3B 1.5 ≧180 ≧400 1.5 EM500-2R2G/3R0P-1B/2B/3B 2.2 ≧180 ≧400 1.5 EM500-4R0G/5R5P-3B 4 ≧90 ≧800 2.5 EM500-5R5G/7R5P-3B 5.5 ≧60 ≧1000 4 EM500-7R5G/9R0P-3B 7.5 ≧60 ≧1000 4 EM500-011G/015P-3B 11 ≧30 ≧2000 6 EM500-015G/018P-3B 15 ≧30 ≧2000 6 EM500-018G/022P-3B 18.5 ≧30 ≧2000 6 EM500-022G/030P-3/3B 22 ≧15 ≧4000 6 EM500-030G/037P-3/3B 30 ≧15 ≧4000 6 EM500-037G/045P-3/3B 37 ≧10 ≧6000 6 EM500-045G/055P-3/3B 45 ≧10 ≧6000 6 EM500-055G/075P-3/3B 55 ≧7.5 ≧8000 6 EM500-075G/090P-3/3B 75 ≧6 ≧8000 6