sinee — 11.3 Options of Cable

EM600 High-Performance Vector Control Inverter User Manual connected in parallel, the bus in connection should be amplified accordingly. Single-phase inverter selects voltage withstanding type cable of AC300 V, 3-phase inverter uses cable of over AC450V and temperature resistance 105 ℃ . 11.2 Braking Unit If EM600 inverter (over 18.5 kW) has no built-in braking unit (22 – 75 kW optional internal braking unit), then user shall select our BR100 braking units (power range: 18.5 – 315 kW). Models of braking units are listed below: ★ When BR100-106 adopts minimum resistance, it can continue to work if braking frequency of braking unit D=33%.

If D>33%, it needs to work intermittently, otherwise an overheat protection fault will occur. 11.3 Options of Cable Because all braking units and braking resistors wok at high voltage (>400VDC) discontinuously, please select appropriate cable. See Table 11-1 for specification of cable of main circuit. During wiring, only cable with insulation grade and section meeting standards shall be used. Table 11-1 Cable for Braking Unit and Braking Resistor Flexible cable has better flexibility. Since cable may contact high-temperature device during use, it’s better to use copper core or heat-proof flexible cable or fire-retardant cable.

Braking unit and inverter shall be as close as possible to each other, and it’s better to keep 246 Minimum Average braking Peak current Inverter power Model No. Application resistance (Ω) current I (A) av I (A) max (kW) BR100-045 Energy consumption brake 10 45 75 18.5 - 45 BR100-160 Energy consumption brake 6 75 150 55 - 160 BR100-315 Energy consumption brake 3 120 300 185 - 315 Model No. Average braking current Peak current I (A) max Section of copper core I (A) av cable (mm2) BR100-045 45 75 10 BR100-160 75 150 16 BR100-315 120 300 25