EM600 High-Performance Vector Control Inverter User Manual 12.3.3.5 Function Code 0x06 Write Single Register or Command This function code is used to write single holding register in remote device. Request PDU describes address of written register. Normal response is a response to request and returned after writing register. Request PDU Response PDU Incorrect PDU The following is an example of requesting to change motor 1 drive control mode (F00.01) t o 2: FVC: ★ Frequently changed function codes of inverter can not complete this with 0x06 to avoid damaging inverter.
0x41 RAM & EEPROM, a user-defined function code, corresponds to standard common function code 0x06; the definition of this function code is the same as corresponding standard function code (in request, response and error PDU). The only difference is that when this function code is enabled, only corresponding value of RAM is modified, without being saved to EEPROM (holding register). For those function codes that are often changed, like F00.07, it’s recommended to use 0x41 (user can also operate 7001H directly by modifying main frequency source A, refer to 12.3.3.2 and 12.3.4 for details) to avoid damaging inverter.
See the following description 258 Request Response Field Name Field Name Field Name (0x) (0x) (0x) (normal) (abnormal) Function 08 Function 08 Function 88 00 Sub-Function 00 03 Sub-Function Code Hi Code Hi Exception 00 Sub-Function 00 Code Sub-Function Code Lo Code Lo Data Hi A5 Data Hi A5 Data Lo 37 Data Lo 37 Function Code 1 byte 0x06 Register Address 2 bytes 0x0000 - 0xFFFF Register Value Hi 2 bytes 0x0000 - 0xFFFF Function Code 1 byte 0x06 Register Address 2 bytes 0x0000 - 0xFFFF Register Value Hi 2 bytes 0x0000 - 0xFFFF Error Code 1 byte 0x86 Exception Code 1 byte See Table 12-4 Request Response Field Name (0x) Field Name (normal) (0x) Field Name (abnormal) (0x) Function 06 Function 06 Function 86 Register Address Hi 00 Register Address Hi 00 03 Exception Code Register Address Lo 01 Register Address Lo 01 Register Value Hi 00 Register Value Hi 00 Register Value Lo 02 Register Value Lo 02