EM600 High-Performance Vector Control Inverter User Manual for details. Data above means to change set frequency (F00.07) to 50.00Hz, which will take effect immediately, but will not be saved in EEPROM. After rewriting, inverter runs at 50.00 Hz, but runs at set frequency prior to change after inverter is powered on. 12.3.3.6 Function Code 0x10 Write Multiple Registers or Commands This function code is used to write continuous register blocks (1 to 16 registers) in a remote device. Value requested for writing is described in request data field. Each register divides data into two bytes. Normal response is to return function code, initial address and number of registers written.
Request PDU N*=Number of Registers Response PDU Incorrect PDU The following is an example of requesting to write 00 01 and 00 03 in the two registers starting from F03.00, i.e., setting functions of output terminals Y1 and Y2.
259 Request Response Field Name (0x) Field Name (normal) (0x) Function 41 Function 41 Register Address Hi 00 Register Address Hi 00 Register Address Lo 07 Register Address Lo 07 Register Value Hi 13 Register Value Hi 13 Register Value Lo 88 Register Value Lo 88 Function Code 1 byte 0x10 Initial Address 2 bytes 0x0000 - 0xFFFF Number of Registers 2 bytes 1 - 16 Number of Bytes 1 byte 2×N* Register Value N*×2 bytes Function Code 1 byte 0x10 Initial Address 2 bytes 0x0000 - 0xFFFF Number of Registers 2 bytes 1 - 16 Error Code 1 byte 0x90 Exception Code 1 byte See Table 12-4 Request Response Field Name (0x) Field Name (normal) (0x) Field Name (abnormal) (0x) Function 10 Function 10 Function 90 Initial Address Hi 03 Initial Address Hi 03 03 Exception Code Initial Address Lo 00 Initial Address Lo 00 Number of Registers Hi 00 Number of Registers Hi 00 Number of Registers Lo 02 Number of Registers Lo 02 Number of Bytes 04 Register Value Hi 00 (F03.00)