sinee — 12.4.1 Definitions of Interframe and Intraframe Time Intervals

EM600 High-Performance Vector Control Inverter User Manual 12.3.7 Abnormal Information Response Master wants to receive a normal response after it sends a request to slave. Inquiry of master can possibly result in the following four response situations:  If slave has received a request without communication error and can handle inquiry normally, slave will return a normal response;  If slave has not received a request due to communication error, slave can not return information. Slave will be deemed as overtime;  If slave has received a request but detected a communication error (for example parity, address, frame error), it will not return a response.

Slave will be deemed as overtime;  If slave has received a request without communication error but can not handle it (example: request to read a register which does not exist and so on), it will return an abnormal response to report actual situation of error to master. An abnormal response message has two fields different from the normal response:  Function code field: in normal response, slave copies original request function code from appropriate function code field. MSB of all function codes is zero. In abnormal response, MSB of slave function code is 1. Abnormal response function code = normal function code +0x80  Data Field:

A slave can return data in data field in normal response and return abnormal code in abnormal response. See Table 12-4 for definitions of exception codes. Table 12-4 Definitions of Exception Codes 12.4 Protocol Description 12.4.1 Definitions of Interframe and Intraframe Time Intervals A complete MODBUS message includes not only required data unit, but also start and end 267 Exception Name Definitions Code 01H Illegal function Function code received by slave exceeds configured scope (rer to 12.3.3 Function Code).

02H Illegal data address Data address received by slave (inverter) is not a permitted one; especially, combination of start address and transmission length of register is invalid (refer to 12.3.4 Allocation of Register Address). 03H Illegal data frame As detected by slave (inverter), inquiry data frame length or CRC parity is incorrect. 04H Slave fault Unrecoverable error occurs when slave (inverter) tries to execute require operation. Possible causes include logic error and failure to write EEPROM. 05H Data exceeding the range Data received by slave (inverter) exceeds corresponding register scope: minimum - maximum. 06H Parameter:

read only Present register is read only and can not be written. 07H Parameter: not modified during running Inverter is in running status. Present register can not be written. If necessary, please stop inverter at first. 08H Parameter: password protection Present register is password protected.