sinee — 12.5 Example

EM600 High-Performance Vector Control Inverter User Manual 5) Check whether lines work Send: 01 08 00 00 AA 55 5E 94 Return: 01 08 00 00 AA 55 5E 94 (Normal) Return: 01 88 04 47 C3 (When abnormal, assuming that slave fails) 6) Change carrier frequency (F00.23) to 4.0 kHz. (Since such function codes are expected to be saved in EEPROM usually after change, 0x06 is used hereby). Send: 01 06 00 17 00 28 39 D0 Return: 01 06 00 17 00 28 39 D0 (Normal) Return:

01 86 04 43 A3 (When abnormal, assuming that slave fails) 271 Send Normal return Abnormal return 4 Initial Address Lo 00 Register Value Hi (F19.00) 00 CRC Parity Lo 40 5 Number of 00 Register Value Lo (F19.00) 11 CRC Parity Hi F3 Registers Hi 6 Number of 06 Register Value Hi (F19.01) 00 Registers Lo 7 CRC Parity Lo C1 Register Value Lo (F19.01) 00 8 CRC Parity Hi 4C Register Value Hi (F19.02) 00 9 Register Value Lo (F19.02) 00 10 Register Value Hi (F19.03) 01 11 Register Value Lo (F19.03) 2C 12 Register Value Hi (F19.04) 00 13 Register Value Lo (F19.04) 00 14 Register Value Hi (F19.05) 00 15 Register Value Lo (F19.05) 00 16 CRC Parity Lo 53 17 CRC Parity Hi 5B * Frame End ≥3.5 idle characters Send Normal return Abnormal return * Frame Header ≥3.5 idle characters 1 Address 01 Address 01 Address 01 2 Function 08 Function 08 Function Code 88 3 Sub-Function Code Hi 00 Sub-Function Code Hi 00 Exception Code 04 (assumption) 4 Sub-Function Code Lo 00 Sub-Function Code Lo 00 CRC Parity Lo 47 5 Data Hi AA Data Hi AA CRC Parity Hi C3 6 Data Lo 55 Data Lo 55 7 CRC Parity Lo 5E CRC Parity Lo 5E 8 CRC Parity Hi 94 CRC Parity Hi 94 * Frame End ≥3.5 idle characters Send Normal return Abnormal return * Frame Header ≥3.5 idle characters 1 Address 01 Address 01 Address 01