EM600 High-Performance Vector Control Inverter User Manual 2) Inverter stops Send: 01 41 70 0000 07 66 C7 Return: 01 41 70 0000 07 66 C7 (Normal) Return: 01 C1 04 70 53 (When abnormal, assuming that slave fails) 3) Change the setting frequency (for example 50.00 Hz/1388 H) (F00.04=7) Send: 01 41 70 15 13 88 3B 97 Return: 01 41 70 15 13 88 3B 97 (Normal) Return: 01 C1 04 70 53 (When abnormal, assuming that slave fails) 4) Read last fault information (read F19.00 - F19.05) Send: 01 03 13 00 00 06 C1 4C Return: 01 03 0C 00 11 00 00 00 00 01 2C 00 00 00 00 53 5B (Normal) Return:
01 83 04 40 F3 (When abnormal, assuming that slave fails) 270 Send Normal return Abnormal return * Frame Header ≥3.5 idle characters 1 Address 01 Address 01 Address 01 2 Function Code 41 Function Code 41 Function Code C1 3 70 70 04 (assumption) Register Address Hi Register Address Hi Exception Code 4 Register Address Lo 00 Register Address Lo 00 CRC Parity Lo 70 5 Register Value Hi 00 Register Value Hi 00 CRC Parity Hi 53 6 Register Value Lo 07 Register Value Lo 07 7 CRC Parity Lo 66 CRC Parity Lo 66 8 CRC Parity Hi C7 CRC Parity Hi C7 * Frame End ≥3.5 idle characters Send Normal return Abnormal return * Frame Header ≥3.5 idle characters 1 Address 01 Address 01 Address 01 2 Function Code 41 Function Code 41 Function Code C1 3 Register Address Hi 70 Register Address Hi 70 Exception Code 04 (assumption) 4 Register Address Lo 15 Register Address Lo 15 CRC Parity Lo 70 5 Register Value Hi 13 Register Value Hi 13 CRC Parity Hi 53 6 Register Value Lo 88 Register Value Lo 88 7 CRC Parity Lo 3B CRC Parity Lo 3B 8 CRC Parity Hi 97 CRC Parity Hi 97 * Frame End ≥3.5 idle characters Send Normal return Abnormal return * Frame Header ≥3.5 idle characters 1 Address 01 Address 01 Address 01 2 Function Code 03 Function Code 03 Function Code 83 3 Initial Address Hi 13 Number of Bytes 0C Exception Code 04 (assumption)