EM600 High-Performance Vector Control Inverter User Manual rate is 9600 bps, minimum response delay shall be 5 ms (3.5Ч10/9600+1=4.64≈5). If communication data involves EEPROM operation, actual time interval will be extended. [ 7 ]: Valid data frame: sent by external master (other than keypad) to inverter, and function code, data length and CRC are correct. In Figure 12–4, data sending section (t s ), sending end mark section (t w1 ), 75176 forwarding waiting section (t w2 ), data return section (t r ) and 75176 receipt section (t w3 ).
t w3 t t s t w1 t w2 t r Figure 12-4 Time Sequence Learning of Complete Data Frame 12.4.4 Communication Overtime Communication interval △ t refers to the period from previous receipt of a valid data frame by slave (inverter) to its receipt again. If △ t is greater than set time (see F10.03; this function is disabled if it is set as 0), this is called “communication overtime”. Figure 12-5 485 Network Link Data 12.5 Example 1) Forward Running of inverter Send: 01 41 70 00 00 01 E6 C5 Return: 01 41 70 00 00 01 E6 C5 (Normal) Return:
01 C1 04 70 53 (When abnormal, assuming that slave fails) 269 Send Normal return Abnormal return * Frame header ≥3.5 idle characters 1 Address 01 Address 01 Address 01 2 Function Code 41 Function Code 41 Function Code C1 3 70 70 04 (assumption) Register Address Hi Register Address Hi Exception Code 4 Register Address Lo 00 Register Address Lo 00 CRC Parity Lo 70 5 Register Value Hi 00 Register Value Hi 00 CRC Parity Hi 53 6 Register Value Lo 01 Register Value Lo 01 7 CRC Parity Lo E6 CRC Parity Lo E6 8 CRC Parity Hi C5 CRC Parity Hi C5 * Frame End ≥3.5 idle characters