EM600 High-Performance Vector Control Inverter User Manual 5 Trial Operation 5.1 Trial Operation Procedure Follow steps in table 5–1 for trial operation of EM600 inverter. Table 5-1 Steps of Trial Operation 53 Step Description Check power of inverter and install inverter as per requirements in Chapter 2. Installation Inverter Wiring Wiring as per the requirements in Chapter 3.
Verify that input power is connected correctly and input power supply circuit is already connected to circuit breaker; inverter is grounded; power line is connected to inverter power supply input terminals R, S and T; motor is properly connected to output terminals U, V and W of inverter; braking resistor is connected between + and PB; control circuit is properly connected and all limit switches and brake control terminals are connected. Check before Power-on Check whether there is abnormal sound, foreign odor, fume or the like of inverter. Check whether power indicator is on and whether the operation panel displays normally or there is no fault alarm.
In case of fault, please cut the power and check it as per Chapter 9. Power-on Check Parameter Setting Macro setting is applied (if any). Please input nameplate parameters of motor driven by inverter and check input carefully, otherwise serious problems can occur during running. Set parameters of motor 1 in F01 group. If two motors are used in parallel, then either rated power or rated current shall be the sum of that of two motors. If two motor switches extra motor parameters should be set in F14 group.
Correctly Input Motor Nameplate Parameter Properly set inverter and motor limit parameters and protection parameters, mainly including maximum frequency, upper limit frequency and fault output. For hoisting equipment, the following protection settings shall be invalid: current limit protection and overvoltage stall protection. Protection Parameter Setting of Motor and Inverter Before running for the first time, please conduct motor parameter autotuning, in order to obtain Motor Parameter Autotuning